Abstract
In order to improve the reliability and the quality of stationary valve regulated lead acid (VRLA) batteries, the failure modes of the stationary VRLA batteries which caused by the water loss and the thermal runaway are studied. The water loss may be solved by increasing the Oxygen recombination efficiency, choosing the suitable grid material and the additives of megative paste, decreasing the corrosion of the positive plates. The thermal runaway may be solved by decreasing the inner ohmic resistance of VRLA batteries, improving the outside condition of batteries such as putting into the absorbing heat material between the abtteries etc..
Keywords
VRLA batteries, Water loss, Thermal runaway
Publication Date
1997-08-28
Online Available Date
1997-08-28
Revised Date
1997-08-28
Received Date
1997-08-28
Recommended Citation
Yibo Tong, Xiangming Qiu.
Studies on the Failure Modes of Stationary VRLA Batteries[J]. Journal of Electrochemistry,
1997
,
3(3): Article 12.
DOI: 10.61558/2993-074X.3130
Available at:
https://jelectrochem.xmu.edu.cn/journal/vol3/iss3/12
References
1张廷鹏.现代通信供电系统.北京:人民出版社,1996:12BCulpin.Failuremodesoflead/acidbatteries.J.Power.Sources,1991,36:4153HTuphorn.Sealedlead/acidbateries:Theoryandaplication.Ibid.,1990,31:574JYamashita.CrystalgrowthofPbO2anditsrelationtothecapacitylossofpositiveplatesinsealedlead/acidbateries.Ibid.,1990,30:135RPeatetal.Aphotocurrentimagingstudyofthedistributionofleadmonoxideincorosionlayersonlead/acidbaterygrids.Ibid.,1993,42:1196朱松然.密封铅蓄电池负极膨胀剂的选择.蓄电池.1993,1:27JSzymboriki.MakingVRLAcelsmorereliable.BateriesInternational,1994,19:448DMcMenamin.Astudyonthermalrunaway.Ibid.,1993,14:819SimonGBarnes.ThermalmanagementofEVbatteries.Ibid.,1995,23:76
Included in